Siemens DT-11
A Thermal Fire Detector i s of fixed-temperature type. Designed for plug-in use with the standard Fire Safety Series 11 detector base. The thermal fire detector’s element i s self-restoring. The thermal fire detector’s electronics will lock in on ce the alarm i s triggered. The temperature rating for the thermal fire detector i s 135°F (58°C). A lamp i s located on the base of the detector to indicate the initiation of an alarm.
The Thermal Fire Detector, which i s shock and corrosion-resistant, responds only to heat. It i s suitable for use in areas where normal conditions would prohibit the use of other types of detectors. Wh en connected to fire-safety equipment, the detector i s fully compatible with fire-safety ionization detectors. Photoelectric detectors, flame detectors, and manual stations. To operate its alarm-indicating lamp. The thermal fire detector can operate 1 remote indicating lamp or remote relay wh en desired. The engineer shall install the detectors with #18 AWG thermoplastic wire with a 300-volt insulation rating.
Features / Specifications
Self-testing with status-indicating, multi-color LED
Simple twist/lock assembly
Alarm lock-in
Remote function output
Screw-clamp terminals
• UL and ULC Listed; FM, CSFM & NYMEA Approved
Temperature: 32°F (0°C) to 100°F (38°C)
Humidity: Up to 93% RH, non-condensing
Alarm Temperature: 135°F (57°C)
Voltage: 16-27 VDC
Ripple: 3V peak-to-peak
Supervisory Current: 110μA max
Alarm Current: 33-50 mA
Air Pressure: No effect