The Siemens ILI-1B comes designed specifically for use with Fire Safety AD-3I air duct detector housing, and, like the ILI1A, contains a specially designed internal chamber cover. The Siemens ILI-1B must be used with the AD-3I air duct detector housing in air duct applications with air velocities of 500-4000 ft./min. If a relay is desired, use a DA-X3SR module with the AD-3I housing.
The ILI Series ionization detectors are compatible with the Fire Safety SensorLINK FPI-32 or DPU field programmer/tester. The FPI-32 is a compact, portable, menu-driven accessory that makes programming and testing detectors faster, easier, and more reliable than other methods. The FPI-32 eliminates the need for cumbersome, unreliable mechanical programming methods and reduces installation and service costs by electronically programming addresses and functionally testing the ILI’s performance before the detector is installed.
The ILI Series detectors are compatible with Fire Safety IXL, MXL, and XL3 control panels. All ILI Series detectors come from Underwriters Laboratories Listed.
Features/ Specifications
Current Requirements: Normal – 1.2mA Typical Alarm – 1.5mA Typical
Voltage Range: *16VDC – 30VDC Peak Pulsed Voltage
Operating Temperature: +32o F (0o C) to +100o F (38o C) per UL 268/268A
Humidity: 0-93% Relative Humidity Non-Condensating
Addressable ionization detector air duct use only(with AD-3I)