General
A backlit LCD annunciator for the NOTIFIER fire alarm control panels, or network control annunciators. That supports the 80-character display format. LCD2-80s may b e connected to the four-wire EIA-485 terminal port.
The Fire alarm annunciator mimics the display of NFS2-640, NFS2-3030, NFS-320, NCA-2, and legacy panels. That supported the LCD80/LCD-80TM.
Features
80-character backlit Liquid Crystal Display, 20 characters x 4 lines.
The display mimics the panel or NCA:
Event message.
20 characters for point label.
12 characters for extended label.
Time, date, and point address.
Control switches for System Acknowledge, Signal Silence Drill, and System Reset.
LEDs for general off-normal events with UL 864 9th Edition Panels.
ACS mode option for annunciation of user-selected points.
Up to 6000-foot segments between units.
Local piezo sounder with alarm/trouble resound.
Displays all analog, addressable points.