Simplex 4100-3109 IDNet 2 Module
The Simplex IDNet 2 Module provides standard addressable device communications. IDNet-compatible devices accept optional modules for communications with MAPNET II-compatible devices. They are using a two-wire communications circuit. Individual devices like manual fire alarm stations, TrueAlarm sensors, and conventional IDC zones. Sprinkler water flow switches can be interfaced with the addressable controller to communicate their identity and status.
Addressability allows the location and condition of the connected device to be displayed on the operator interface LCD. And remote system annunciators. With addressable devices and control circuits (fans, dampers, etc.). May be individually controlled and monitored.
Each Simplex 4100-3109 addressable device on the communication channel is continuously interrogated for status conditions. Class B and Class A operations a re available. Sophisticated poll and response communication techniques ensure supervision integrity. And allow for “T-tapping” of the circuit for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications poll. Which can be turned on steadily from the panel.
The CPU bay ES-PS provides an IDNet 2 signaling line circuit. That supports up to 250 addressable monitor and control points intermixed on the same pair of wires. IDNet 2 and IDNet 2+2 Module SLCs are isolated from other system reference voltages. To reduce common-mode noise interaction with adjacent system wiring. Additional 250 address IDNet 2 or IDNet 2+2 Modules are available.