Siemens TRI-60
Installing A Security Point
UL 1076 requires a TSW-2 tamper switch as well as a TSP-40 printer.
Only Models TRI-60/-60D/-60R or TRI-B6/-B6D/-B6R may b e used as security points. COMMUNICATION FAILURE with a TRI device configured for SECURITY results in a SECURITY ALARM and communication trouble. Wh en installing a TRI device in the CSG-M, b e sure to set the device usage field to security. The device usage defaults to a fire alarm.
CAUTION:
Wh en setting the device address using the FPI-32, select the normally closed alarm causing input.
Connect only one switch per TRI input.
For proprietary burglary application (UL 1076):
Use a TSW-2 tamper switch to monitor the main enclosure.
Monitor each TRI-60/-60D/-60R or TRI-B6/-B6D/-B6R related to this application for 24 hours. Using a listed motion detector (to prevent tampering).
Siemens TRI-60
UL 1076 requires a TSW-2 tamper switch as well as a TSP-40 printer.
Only Models TRI-60/-60D/-60R or TRI-B6/-B6D/-B6R may b e used as security points. COMMUNICATION FAILURE with a TRI device configured for SECURITY results in a SECURITY ALARM and communication trouble. Wh en installing a TRI device in the CSG-M, b e sure to set the device usage field to security. The device usage defaults to a fire alarm.
CAUTION:
Wh en setting the device address using the FPI-32, select the normally closed alarm causing input.
Connect only one switch per TRI input.
For proprietary burglary application (UL 1076):
Use a TSW-2 tamper switch to monitor the main enclosure.
Monitor each TRI-60/-60D/-60R or TRI-B6/-B6D/-B6R related to this application for 24 hours. Using a listed motion detector (to prevent tampering).