The Notifier XP6-MA provides an interface between the intelligent alarm system as well as a two-wire conventional detection zone. Also, a common SLC input is used for all modules, and the initiating device circuits share a common external supervisory supply and ground. Otherwise, each module operates independently from the others. Also, the Notifier XP6-MA transmits the status of a zone of two-wire detectors to the fire alarm control panel. In addition, the interface module supervises the zone of detectors and the connection of the external power supply.
The first module is addressed from 01 to 154 while the remaining modules are automatically assigned to the next five higher addresses. Besides, provisions come included for disabling a maximum of two unused modules. Furthermore, each XP6-MA module has panel-controlled bi-color LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
Features / Specifications
- Status indicators for each point
- Rotary address switches
- Class A or Class B operation
- Up to two unused addresses
- Six addressable Class B or three addressable Class A initiating device circuits.
- Removable 12 AWG (3.1 mm²) to 18 AWG (0.78 mm²) plugin terminal blocks.
- FlashScan® or CLIP operation
- Mount up to six modules on a CHS-6 chassis in a CAB-3 Series, CAB-4 Series, BB-25 cabinet (optional), or EQ Cabinet Series.
- Temperature range: 32°F to 120°F (0°C to 49°C)
- Humidity: 10% to 85% noncondensing.
Reviews
There are no reviews yet.