The Edwards SD-T8 is a duct smoke detector air sampling tube used as part of Edwards/EST SuperDuct fire detection systems. It is not itself a smoke detector; instead, it is an accessory that extends into HVAC ductwork and directs sampled airflow through a compatible duct smoke detector.
Edwards documentation identifies the SD-T8 as an 8-inch sampling tube and lists it among the sampling-tube options for intelligent and conventional SuperDuct detectors. Current Edwards documentation for the SIGA-DDOS also continues to list the SD-T8 as an available accessory.
Product Functions
- Samples air from HVAC ductwork
- Works as part of a duct smoke detection system
- Directs representative duct airflow into the detector
- Supports detection of smoke transported through HVAC systems
- Designed for Edwards SuperDuct detector assemblies
- 8-inch nominal sampling-tube length
- Suitable for relatively narrow HVAC ducts
- Installs through the duct detector housing
- Can be installed from the front or back side of compatible detector housings
- Uses inlet openings positioned toward the direction of airflow
- Available as one of several Edwards SD-T-series sampling-tube lengths
Air Sampling Function
The primary purpose of the SD-T8 is to allow a compatible duct smoke detector to sample air moving through an HVAC duct.
The tube extends into the duct so that its inlet openings encounter the moving airstream. Air collected by the tube is routed through the duct detector’s sensing arrangement, where the associated smoke detector evaluates the sample for the presence of smoke.
This arrangement allows a duct detector to monitor air moving through HVAC equipment without placing the detector’s entire electronics assembly inside the duct.
8-Inch Sampling Tube
Nominal Tube Length: 8 inches
The SD-T8 is the shortest model identified in the common Edwards SuperDuct sampling-tube family. Manufacturer documentation lists the following tube options:
SD-T8: 8 inches
SD-T18: 18 inches
SD-T24: 24 inches
SD-T36: 36 inches
SD-T42: 42 inches
SD-T60: 60 inches
SD-T78: 78 inches
SD-T120: 120 inches
The appropriate tube is selected primarily according to the width of the HVAC duct being monitored.
Compatible Duct Width
Published distributor specifications for the SD-T8 identify a compatible duct-width range of:
Minimum Duct Width: 7 inches
Maximum Duct Width: 12 inches
Correct tube selection is important because the sampling arrangement must extend appropriately into the duct to obtain a representative airflow sample.
SuperDuct Compatibility
Edwards documentation lists the SD-T8 as an accessory across multiple generations/configurations of its SuperDuct products.
Documented applications include conventional SuperDuct detectors as well as Edwards intelligent duct detector products. The SD-T8 is specifically listed in documentation for products including the E-PDD Intelligent Duct Detector and conventional SD-2W systems.
Current Edwards documentation also lists the SD-T8 among the accessories for the SIGA-DDOS Optica Duct Smoke Detector, indicating continued use of this sampling-tube format.
Newark additionally specifies compatibility with the Edwards SD-4WJ four-wire duct smoke detector.
Sampling Tube Construction
The SD-T-series tubes are described as rigid metal sampling tubes.
The rigid construction allows the tube to maintain its position across the duct’s airstream after installation.
Unlike an electrical detector component, the SD-T8 does not require a power supply, signaling circuit, address, relay, or field wiring of its own.
Installation
The SD-T8 is installed in conjunction with a compatible Edwards duct smoke detector housing.
Typical installation involves:
- Selecting the sampling tube according to duct width
- Determining duct airflow direction
- Installing the duct detector housing in the required location
- Inserting the SD-T8 through the detector and into the duct
- Orienting the sampling holes toward the incoming airflow
- Securing the tube to the detector assembly
- Confirming that the sampling tube is correctly positioned within the duct
- Testing the completed duct detector installation
Edwards-compatible documentation indicates that the sampling tube is ordered separately from certain detector assemblies.
Newark notes that the rigid sampling tubes may be installed from either the front or back side of the detector housing without opening the detector.
Airflow Considerations
The sampling tube must interact correctly with the duct airflow for the complete smoke detector assembly to operate as intended.
For example, Edwards’ SuperDuct two-wire detector documentation specifies an overall detector air-velocity rating of 100 to 4,000 ft/min and an air-pressure differential range of 0.005 to 1.00 inches of water. These are specifications of the associated detector system rather than standalone ratings of the SD-T8 tube itself.
This distinction is important: the SD-T8 is a passive sampling accessory, so electrical and smoke-sensitivity specifications belong to the detector with which it is installed.
Physical Specifications
Product Type: Air Sampling Tube
Nominal Length: 8 in
Published Overall Height/Length: 8 in
Published Overall Width: 0.5 in
Construction: Rigid metal
Mounting Location: HVAC duct
Compatible Duct Width: 7–12 in
Edwards’ E-PDD documentation lists an approximate shipping weight of:
Shipping Weight: 0.5 lb / 0.2 kg
Electrical Specifications
The SD-T8 has no standalone electrical specifications because it is a passive air-sampling tube rather than an electrically powered detection device.
Therefore, specifications such as:
- Operating voltage
- Standby current
- Alarm current
- Relay rating
- Smoke sensitivity
- Address range
are determined by the compatible Edwards duct detector, not by the SD-T8.
Testing & Maintenance
Inspection of an SD-T8 installation should include checking:
- Sampling tube is securely installed
- Tube has not become loose or displaced
- Sampling openings are unobstructed
- Tube orientation remains correct relative to airflow
- Tube is appropriate for the duct width
- Detector housing remains securely mounted
- Airflow through the detector remains adequate
- Complete duct detector passes required functional testing
Testing requirements should follow the instructions for the specific Edwards duct detector used with the SD-T8.
Product Identification
- Manufacturer/Brand: Edwards / Edwards Signaling
- Model: SD-T8
- Product Type: Air Sampling Tube
- Product Family/Application: SuperDuct
- Nominal Length: 8 inches
- Construction: Rigid metal
- Installation Location: HVAC duct
- Compatible Duct Width: approximately 7–12 inches
- Function: Duct air sampling for smoke detection
- Approx. Shipping Weight: 0.5 lb / 0.2 kg
- Electrical Power Required: None
- Field Wiring Required: None for the tube itself
- UPC: 793016035585 (published distributor listing)
Applications
Suitable for:
- HVAC Duct Smoke Detection
- Fire Alarm Systems
- Edwards SuperDuct Systems
- Intelligent Duct Smoke Detectors
- Conventional Duct Smoke Detectors
- Air-Handling Systems
- Supply-Air Ducts
- Return-Air Ducts
- Commercial HVAC Systems
- Institutional Buildings
- Schools and Universities
- Hospitals and Healthcare Facilities
- Office Buildings
- Hotels
- Industrial Facilities
- Warehouses
- Commercial Buildings