The Simplex 4004 supports only one 2-IDC expander module in a system. Also, the Simplex 4004 2-IDC expander module is use to expand the system to four or eight zones. Besides, each module terminates for two Style B initiating circuits. Each circuit supports 2 mA of detector current (supervisory). Zone disconnect switches are provided on each IDC zone circuit. An open collector output for each circuit is activate on a short or current limited condition. In addition, this output can drive and supervise a remote hardwired annunciator or auxiliary relay load (Air Products) of 150 mA. A 6.8K ohm EOL is require.
The two NACs available with the base 4004 panels are rate at 2-amperes at 24-volts for each circuit. Power-limiting is from the Simplex 4004 system power supply. Additional NACs are add using the 4009 NAC Power Extender. The Simplex 4004 is a general alarm system, meaning that both NACs are energize on any alarm. Selection of “On Until Silenced” or “On Until Reset” is possible using jumper switch settings. The back box for the 4004 mounts between two studs, 16 inches on center. Flush mounting or semi-flush mounting is possible with a left-hinged door.