The Genesis Est Edwards G1F-HDVM horn strobe is a fire alarm notification appliance designed for indoor walls. Also, there are field-configurable options for selecting dB output, horn signal, or strobe signal output. Besides, the strobe includes a field-configurable switch for selecting the desired candela output. The candela output setting is locked in place, likewise, remains visible after final installation.
In fact, The Genesis Est Edwards G1F-HDVM strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired and the latest Canadian standard CAN/ULC-S526. Additionally, the synchronized operation requires a separately installed synchronization control module. Install this device in accordance with applicable requirements in the latest editions of the NFPA codes together with standards; the National Building Code of Canada; the Canadian Electrical Code, Part 1, Section 32, as well as in accordance with the local authorities having jurisdiction.
Features / Specification
- Operating Voltage: 24 VDC or 24 VFWR nominal
- Light output: Selectable at 15, 30, 75, and 110 cd
- Default settings: 1 flash per second (fps)
- Wire size: 12 to 18 AWG (0.75 to 2.50 mm²)
- Temperature: 32 to 120°F (0 to 49°C)
- Relative humidity: 0 to 93% noncondensing
- Compatible electrical boxes: 2-1/2 in. (64 mm) deep single-gang box 4 in. square box 1-1/2 in. (38 mm), 2-gang 4 in. octagonal with G1T or G1RT trim accessory
- Synchronization: Maximum allowed resistance between any two devices is 20 Ω. Refer to specifications for the synchronization control module, this strobe, as well as the control panel to determine allowed wire resistance.