The Honeywell MS-7ASF Addressable Single-Action Pull Station is a Gamewell-FCI intelligent initiating device designed for installation on the signaling line circuit (SLC) of compatible Gamewell-FCI analog addressable fire alarm control panels. When activated, the station reports its individually assigned address to the control panel.
The MS-7ASF uses single-action pull operation, incorporates a status LED, and includes a key-operated test/reset lock. Honeywell’s current documentation identifies it specifically as the single-action addressable version of the MS-7 Series.
Product Functions
- Provides addressable fire alarm initiation
- Uses single-action operation
- Communicates its individual address to the control panel
- Uses Velociti communication
- Provides local LED status indication
- Includes key-operated test and reset
- Uses screw-terminal field connections
- Supports surface mounting
- Supports semi-flush mounting
- Includes engraved operating instructions
- Includes Braille text on the operating handle
- Designed for compatible Gamewell-FCI analog addressable systems
Single-Action Operation
The MS-7ASF is specifically a single-action station. Unlike the MS-7AF double-action version, it does not require a preliminary push action before the handle is pulled.
Activation causes the station’s assigned address to register at the compatible fire alarm control panel, allowing personnel to identify the exact initiating-device location.
Velociti Addressable Communication
The MS-7ASF uses the Velociti communication protocol.
Honeywell states that Velociti devices operate in groups during normal polling. When a device changes status, the panel stops group polling and focuses on that specific device, providing response speeds up to five times faster than earlier designs.
The MS-7ASF is intended specifically for Gamewell-FCI analog addressable fire alarm control panels.
LED Status Indication
The station includes an integral LED in the door.
Normal: LED flashes green
Activated/Alarm: LED lights steady red.
Honeywell notes that only the red LED operates when the connected panel does not operate in Velociti mode.
Key Test & Reset
The MS-7ASF includes a tumbler lock for testing and resetting the station.
The lock is keyed alike with compatible Gamewell-FCI fire alarm control panels and other MS-7 Series pull stations, simplifying service access for authorized personnel.
Once the station has been activated, authorized personnel use the key to open and restore the station before resetting the fire alarm system.
Addressable Fire Alarm Operation
The MS-7ASF is an inherently addressable pull station, so a separate monitor module is not normally required when it is connected to a compatible Gamewell-FCI addressable SLC.
The control panel receives the station’s individual address when it is activated, allowing alarm annunciation to identify the programmed point rather than only a conventional initiating zone.
Electrical & Communication Information
Device Type: Addressable pull station
Operation: Single action
Communication: Velociti
Supervisory Current: approximately 0.30 mA
Alarm Current: approximately 3.0 mA, plus LED current
Field Connections: Screw terminals
Status Indicator: Green/red LED.
Electrical compatibility should be verified against the specific Gamewell-FCI control panel and SLC documentation.
Installation Information
The MS-7ASF supports either surface or semi-flush mounting.
Honeywell specifies that interior MS-7 stations can mount on:
Standard double-gang electrical box
or
4-inch square electrical box.
Available mounting accessories include:
SB-10: Surface backbox
BG12TR: Semi-flush trim ring
NY-PLATE: NYC backplate.
After installation, the station should be programmed with its appropriate address and tested to verify activation, LED operation, address reporting, key reset, and normal restoration.