The Firelite MMF-300 is a standard-sized module (typically mounts to a 4″ square box) that supervises either a Style D (Class A) as well as Style B (Class B) circuit of dry-contact input devices.
The Firelite MMF-300 Monitor Module intended for use in intelligent, two-wire systems, where the address selected using rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. Also, the module has a panel-controlled LED indicator.
Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Furthermore, monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. Additionally, a 47K Ohm End-of-Line Resistor (provided) terminates the Style B circuit.
Features / Specifications
- Built-in type identification automatically identifies this device as a monitor module to the control panel.
- Powered directly by two-wire SLC loop. Also, no additional power required.
- High noise (EMF/RFI) immunity.
- SEMS screws with clamping plates for ease of wiring.
- Direct-dial entry of address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems.
- LED flashes during normal operation and latches on steady to indicate alarm.
- operating voltage: 15 to 32 VDC
- current draw: 5.0 mA
- wiring resistance: 1500 Ohms
- Voltage: 11 Volts
- Temperature range: 32°F to 120°F
- Humidity range: 10% to 93% noncondensing
- Resistor not required