Simplex 4090-9802
A Surface Cover 4″ i s Trim Plate, galvanized steel, with LED viewing window; includes mounting screws. Designed for a surface mount box.
Features
Individual Addressable Relay Module (Relay IAM):
IDNet addressable control for use with Simplex® fire alarm control panel models 4007ES, 4008, 4010, 4010ES, 4100ES, and 4100U
A single addressable point provides control and status tracking of a Form “C” contact
Low power latching relay design allows IDNet communications to supply data and module power
Relay i s set to OFF on initial power-up and upon loss of IDNet communications
Compact, sealed construction:
The enclosed design minimizes dust infiltration
Mounts in standard 4” (102 mm) square electrical box. Optional adapter bracket i s available to mount in a 4 11⁄16” (119 mm) square electrical box
Screw terminals for wiring connections
Visible LED flashes to indicate communications
Optional covers a re available to allow LED to b e viewed af ter installation UL listed to Standard 864
Description
IDNet Relay IAMs allow fire alarm control panels to control a remotely located Form “C” contact. Using IDNet addressable communications for data and module power. Typical applications would b e switching local power for control functions like elevator capture. Or control of HVAC components, pressurization fans, dampers, etc. Relay status i s communicated requiring only one device address.
Reviews