Simplex 2098-9737 Supervised Relay
Features
TrueAlarm analog sensing provides a digital transmission of analog sensor values via IDNet or MAPNET II two-wire communications
Fire alarm control panel provides:
Peak value logging allows accurate analysis of each sensor for individual sensitivity selection
Sensitivity monitoring satisfying NFPA 72 sensitivity testing requirements; automatic individual sensor calibration check verifies sensor integrity
Automatic environmental compensation, multi-stage alarm operation, and display of sensitivity directly in percent per foot
Ability to display and print detailed sensor information in plain English language
TrueAlarm Sensor Bases and Accessories
Sensor Base Features
Base mounted address selection:
• Address remains with its programmed location
• Accessible from the front (DIP switch under sensor)
General features:
Automatic identification provides default sensitivity
Integral red LED for power-on (pulsing), or alarm or trouble (steady on)
Locking anti-tamper design mounts on a standard outlet box
Magnetically operated functional test
Sensor Bases
4098-9792, Standard Sensor Base
4098-9789, Sensor Base with wired connections for:
2098-9808 Remote LED alarm indicator or 4098-9822 relay (relay is unsupervised and requires separate 24 VDC)
Supervised Relay Bases (not compatible with 2120 CDT):
The 4098-9791, 4-Wire Sensor Base, used with remote or locally mounted 2098-9737 relay, requires separate 24 VDC
4098-9780, 2-Wire Sensor Base, use with remote or locally mounted 4098-9860 relay, no separate power required
The Supervised relay operation – programmable and can – manually operated from the control panel
Includes wired connections for remote LED alarm indicator or 4098-9822 relay (relay is unsupervised and requires separate 24 VDC)
Simplex 2098-9737 Supervised Relay