The System Sensor SPSRL Wall Speaker Strobe is an indoor audible/visible fire alarm notification appliance designed for emergency voice evacuation systems. It combines a high-fidelity speaker with a clear-lens strobe in a red wall-mount housing marked FIRE.
The SPSRL supports 25V or 70.7V speaker circuits, four selectable speaker power settings, and seven field-selectable strobe intensities. The strobe operates on regulated 12V or 24V notification circuits and supports the System Sensor synchronization protocol.
Product Functions
- Provides emergency voice notification
- Provides visible fire alarm notification
- Combines speaker and strobe functions
- Designed for wall mounting
- Red housing with FIRE marking
- Clear strobe lens
- Supports 25V and 70.7V audio
- Provides four selectable speaker power settings
- Provides seven selectable candela settings
- Supports synchronized strobe operation
- Supports 520 Hz signaling with compatible equipment
- Designed for indoor life-safety notification systems
Selectable Candela
The SPSRL provides seven field-selectable wall-strobe settings:
15 cd
30 cd
75 cd
95 cd
110 cd
135 cd
185 cd.
At the 15 and 30 cd settings, the appliance can automatically accommodate compatible 12V or 24V strobe operation. Higher candela settings require the applicable 24V configuration.
25V / 70.7V Speaker Operation
The speaker supports field-selectable:
25 VRMS
or
70.7 VRMS
audio operation.
This dual-voltage capability allows the SPSRL to integrate with common distributed fire alarm voice evacuation and emergency communication systems.
Selectable Speaker Wattage
The SPSRL provides four speaker power settings:
¼ W
½ W
1 W
2 W.
The speaker has a published frequency range of:
400–4,000 Hz.
Its low total harmonic distortion is intended to provide clear emergency voice reproduction while supporting higher sound output for areas with elevated ambient noise.
520 Hz Capability
The SPSRL is 520 Hz capable when used with compatible fire alarm control equipment.
This capability can support applications requiring low-frequency signaling when the connected fire alarm system provides the appropriate signal.
FIRE Configuration
The specific SPSRL configuration is:
Housing: Red
Marking: FIRE
Lens: Clear
Mounting: Wall
Function: Speaker/Strobe.
System Sensor also produced related plain and Spanish-marked versions, including SPSRL-P and SPSRL-SP.
Synchronized Strobe Operation
The SPSRL supports the System Sensor synchronization protocol.
Synchronization coordinates compatible strobes within the same field of view so that they flash together rather than independently.
Published strobe operation is approximately:
1 flash per second.
Electrical & Audio Information
Speaker Voltage: 25 / 70.7 VRMS
Speaker Taps: ¼ / ½ / 1 / 2 W
Speaker Frequency: 400–4,000 Hz
Strobe Voltage: Regulated 12VDC or 24VDC/FWR
Strobe Output: 15 / 30 / 75 / 95 / 110 / 135 / 185 cd
Flash Rate: 1 flash per second
Wire Range: 12–18 AWG.
The strobe operating range is 8–17.5V for nominal 12V operation and 16–33V for nominal 24V operation when used with compatible built-in synchronization.
Installation Information
The SPSRL uses a plug-in design with a universal mounting plate. The mounting plate incorporates a shorting spring that allows wiring continuity to be checked before the finished appliance is installed.
For surface mounting, System Sensor specifies:
SBBSPRL — Red Surface-Mount Back Box.
The appliance also supports compatible 4-inch square electrical boxes. After installation, speaker voltage, wattage, strobe candela, synchronization, audio output, and circuit supervision should be verified according to the fire alarm system design.