The Simplex 49MTV-WRF i s individually addressed audible/visible notification appliances. That receives power, supervision, and control signals from a Simplex fire alarm control panel. Provides IDNAC Signaling Line Circuits (SLCs). With separate controls on the same two-wire SLC. Installation time and expense for retrofit and new construction can b e signi ficantly reduced.
Wh en Class B wiring i s used; wiring can b e “T” tap. Allowing more savings in the distance, wire, and conduit (size and utilization). And love rall installation efficiency. The use of Self-Test, and Magnet Test features improve installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.
The Simplex 49MTV-WRF provides separate visible and audible notifications using a single two-wire circuit. That confirms connection to the individual notification appliance’s electronic circuit. This operation increases circuit supervision integrity. Providing supervision that extends b eyond the appliance wiring connections.
Features / Specifications
Multi-candela xenon strobe with synchronized 1 Hz flash rate. And with intensity programmable from the control panel. Or jumper selected as 15, 30, 75, 110, 135, or 185 cd
Advanced addressable notification controlled by IDNAC SLCs providing regulated 29 VDC. Allowing strobes to operate with lower current even un der battery backup
520 Hz tone is compliant with NFPA 72 Low-Frequency Signal Requirements for Sleeping Areas
Rugged, high-impact, flame-retardant thermoplastic housing
In/out wiring terminals for 18 AWG to 12 AWG