The Simplex 4098-9751 SSD sensor housing provides two-wire operation (no relay output).
HVAC air ducts in buildings supply fresh air and exhaust stale air. Depending on the overall fire detection requirements, smoke detection may b e required in the air ducts. For applications where sampling tube type duct detection is not appropriate due to low air velocity. Or small duct sizes. Simplex® model 4098-9750 and Simplex 4098-9751 housings can b e used. To install the Simplex model 4098-9714 TrueAlarm analog sensor directly in the duct.
These housings mount a spot-type smoke sensor directly into the duct airflow. Proper application requires controlled dust and humidity.
Features / Specifications
- Remote LED Current: 0.6 mA, no impact to alarm current
- UL Listed Temperature Range: 32° to 100° F (0° to 38° C)
- Operating Temperature Range: 15° to 122° F (-9° to 50° C)
- Humidity Range: 10% to 90% RH from 32° F to 122° F (0° C to +50° C)
- Wiring Connections: Terminal blocks for wire size 18 to 14 AWG (0.82 mm2 to 2.08 mm2)
- Voltage: 18 to 32 VDC
- Alarm Current: 30 mA @ 24 VDC
- Power Limited Contact Rating: Single form “C”, 1 A @ 28 VDC (for suppressed loads)