The Edwards GCF-S7 Genesis Ceiling Speaker is an audible fire alarm notification appliance design for indoor ceilings as well as walls. The speaker includes a field configurable switch for selecting the desired wattage tap. The wattage tap setting comes locked in place and remains visible after final installation. Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code, Part 1, Section 32, and also in accordance with the local authorities having jurisdiction.
Electrical supervision requires the wire run to be broken at each terminal. Furthermore, do not loop the signaling circuit field wires around the terminals. Furthermore, this device meets or exceeds 85 dBA in an anechoic chamber at 10 ft
The Edwards GCF-S7 is not serviceable or repairable. Also, should the unit fail to operate, contact the supplier for replacement. Additionally, perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
Features / Specifications
- Operating voltage: 70 Vrms
- Supervisory voltage: 30 V maximum
- Speaker response: 400 to 4,000 Hz
- Wire size: 12 to 18 AWG
- Temperature: 32 to 120 °F
- Humidity: 0 to 93% RH
Reviews