Firstly, the Genesis Est Edwards GC-S7VM Ceiling Speaker-Strobe is a fire alarm notification appliance designed for indoor ceilings and walls. The speaker-strobe includes field configurable switches for selecting both the desired candela output and wattage tap. Also, these settings are locked in place and remain visible after final installation.
In general, this strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired. Besides, the Synchronized operation requires a separately installed synchronization control module. In addition, install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code.
Installation instructions:
- Open the cover by depressing the tabs on either side of the unit with a small screwdriver. Hinge the cover down, to access the mounting screws and selectable candela and wattage switches. The cover is also detachable for installation convenience.
- If temporal strobe (private mode) operation is desire, cut jumper JP1.
- Connect the speaker and strobe terminals to the signal circuit field wiring. You must observe polarity for the unit to function properly.
- Slide the wattage switch to the desired wattage tap (2 W, 1 W, 1/2 W, or 1/4 W) by aligning it with the indicator below the switch.
Features / Specifications
- Supervisory voltage: 30 V maximum
- Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
- Temperature: 32 to 120 °F (0 to 49 °C)
- Humidity: 0 to 93% RH, noncondensing at 90 °F (32 °C)
- Light output: Selectable at 15, 30, 75, and 95 cd
Reviews
There are no reviews yet.