The Simplex 4009-9401 is individually addressed and receives power, supervision, and control from a TrueAlert Signaling Line Circuit (SLC). Also, for wired control systems, strobe flashes and horn outputs are synchronize per controller. For RUI and IDNet communications control, controllers on the same host control panel are synchronize. (Combination speaker/strobe TrueAlert appliances receive audible control from separate audio circuit wiring.)
Simplex 4009-9401 TrueAlert addressable operation allows strobes to be wire onto the same two-wire SLC circuit as horns but with separately controlled operation. Typical applications are audible notification appliances activate as “on-until-silenced” and visible notification appliances activated as “on-until-reset”. Besides, TrueAlert Addressable Controller diagnostics can be implement from the control panel including silent or active individual appliance magnet test, appliance LED polling indication or all appliance LEDs on.
In addition, address points and custom labels are assign to each TrueAlert appliance allowing troubles to be report individually. Additionally, individual device types are assign and audible appliance coding types are selectable for high or low output (~5 dBA difference) and with operation as Temporal pattern, March Time pattern (60 or 120 bpm), or Steady On.
Features / Specifications
- Supervised wiring connections to each appliance that support using “T-tapped” wiring for Class B circuits
- Horns sounding with selectable high or low output, as Temporal 3 or March Time pattern (60 or 120 bpm), or Steady On, controlled separately from visible appliances on the same two-wire circuit
- Visible appliances operating synchronized at 1 Hz
- Control over power limited, isolated output Signaling
- Control sources selectable to provide individual appliance magnetic test mode and appliance LED polling indicator