In the first place, the Edwards Est SD-TRK and SD-TRM Remote Test Stations are used with SuperDuct series of conventional two-wire and Signature duct smoke detectors. Also, Each remote test station provides a red LED to indicate alarms. Besides, the Edwards Est SD-TRK Remote Reset Test requires a key to activate the test function while the SD-TRM requires the SD-MAG magnetic test tool.
For operating instructions, refer to the following documentation:
- SuperDuct Conventional Two-Wire Duct Smoke Detector Technical Reference (P/N 3100737)
- SuperDuct Signature Duct Smoke Detector Technical Reference (P/N 3100738)
Additionally, for installation instructions see the datasheet below.
Features / Specifications
- Compatible electrical boxes North American 1-gang box Standard 4-in square box, 1-1/2 inches deep, with 1-gang cove
- LED indicators: Alarm (red)
- LED type: Clear lens
- Wire size: 12 to 22 AWG
- Resistance per wire: 10 Ω, max
- Storage temperature: -20 to 60 °C (-4 to 140 °F)
- Operating Temperature: 0 to 55 °C (32 to 131 °F)
- Humidity: 93% RH, noncondensing
- Switch ratings : Voltage: 125 Vdc, max. Current: 4 A, max.
- LED circuit ratings: Voltage: 3 Vdc, max. Current: 30 mA, max.
- Compatible detectors: SuperDuct conventional two-wire as well as Signature duct smoke detectors
Download the Specification sheet in *.pdf format
Reviews