The Notifier FZM-1 Intelligent Interface Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. In conclusion, this module allows intelligent panels to interface and monitor two-wire conventional detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. Actually, all two-wire detectors being monitor must be UL compatible with this module. Besides, the FZM-1 has a panel control LED indicator and can be use to replace an MMX-2 module in existing systems.
In addition, use the Notifier FZM-1 Intelligent Interface Module to monitor a zone of two-wire smoke detectors. Also, the monitor circuit may be wired as an NFPA Style B or Style D Initiating Device Circuit. A 3.9 K Ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 Ohms). In other words install ELR across terminals 8 and 9 for Style D application.
Features / Specifications
- Supports compatible two-wire smoke detectors
- Supervises IDC wiring and connection of external power source.
- SEMS screws with clamping plates for ease of wiring.
- Direct-dial entry of address: 01 – 159 on FlashScan loops, 01 – 99 on CLIP loops.
- LED flashes during normal operation; this is a programmable option.
- LED latches steady to indicate alarm on command from the control panel.
- Normal Operating Voltage: 15 to 32 VDC
- Maximum Current Draw: 5.1 mA (LED on)
- Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Reviews