The Gamewell Fci AOM-2SF allows a Gamewell-FCI analog addressable fire alarm control to switch an external power supply, such as a DC supply or audio amplifier (up to 80 VRMS) to notification appliances. The Gamewell Fci AOM-2SF notification appliance circuit can be wired either Class A (Style Z) or Class B (Style Y). It also supervises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN or SHORT CIRCUIT. The module contains a panel controlled LED.
The Velociti® Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell AOM-2SF analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs.
Features / Specifications
- Compact Size allows easy installation
- Class A, Style Z, or Class B, Style Y notification
appliance circuit - Will accommodate audio amplifiers up to 80 VRMS
- Listed as suitable for releasing device service
- Bicolor LEDS flash green whenever the module is
addressed - Supervisory Current: .000375 amps
- Temperature: 32° to 120° F
Reviews