The FCPS-24S6 Series (6-amp) and FCPS-24S8 Series (8-amp)
are remote power supplies with battery charger. The FCPS-24S6/-
24S8 may be connected to any 12 or 24 volt fire alarm control panel
(FACP) or may be used as stand-alone supplies. Primary applications
include notification appliance circuit (NAC) expansion (to support
ADA requirements and NAC synchronization) or auxiliary power
to support 24 volt system accessories. The FCPS-24S6/-24S8 provides
regulated and filtered 24 VDC power to four notification appliance
circuits configured as either four Class B (Style Y) or Class A
(Style Z, with ZNAC-4 option module). Alternately, the four outputs
may be configured as all non-resettable, all resettable or two nonresettable
and two resettable. The FCPS-24S6/-24S8 also contains
a battery charger capable of charging up to 18 AH batteries. The
FCPS-24S6C and FCPS-24S8C are ULC-listed.
Features
• UL-Listed NAC synchronization using System Sensor®, Wheelock
®, or Gentex® “Commander2” appliances
• Operates as a “sync-follower” or as a “sync-generator” (default)
See note on page 2.
• Contains two fully-isolated input/control circuits – triggered from
FACP NAC (NAC expander mode) or jumped permanently “ON”
(stand-alone mode)
• Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4
module) NACs
• 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load output, with
3 amps maximum/circuit, in NAC expander mode (UL 864)
• 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous output in
stand-alone mode (UL 1481)
• Compatible with coded inputs; signals passed through
• Optional power-supervision relay (EOLR-1)
• In stand-alone mode, output power circuits may be configured as:
resettable, (reset line from FACP required), non-resettable, or a
mix of two and two
• Fully regulated and filtered power output – optimal for powering
four-wire smoke detectors, annunciators, and other system
peripherals requiring regulated/filtered power
• Power-limiting technology meets UL power-limiting requirements
• Form-C normally-closed trouble relay
• Fully supervised power supply, battery, and NACs
• Selectable earth fault detection
• AC trouble report selectable for immediate 2-hour delay
• Works with virtually any UL 864 fire alarm control which utilizes
an industry-standard reverse-polarity notification circuit (including
unfiltered and unregulated NAC power)
• Requires input trigger voltage of 9 – 32 VDC
• Self-contained in compact, locking cabinet – 15”H x 14.5”W x
2.75”D (cm: 38.1H x 36.83W x 6.985D)
• Includes integral battery charger capable of charging up to 18 AH
batteries. Cabinet capable of housing 7.0 AH batteries
• Battery charger may be disabled via DIP switch for applications
requiring larger batteries
• Fixed, clamp-type terminal blocks accommodate up to 12 AWG
(3.1mm2) wire