The Faraday 8705 Conventional Zone Module interfaces an Initiating Device Circuit of conventional devices to an Addressable Device Circuit of an MPC-6000 or MPC-7000 Control Unit. The 8705 can power up to thirty compatible 2-wire, ionization or photoelectric smoke detectors. It can also monitor an unlimited number of contact devices such as waterflow switches, thermal detectors, manual stations, etc. The 8705 may be programmed for alarm verify operation
A Status LED, visible through the cover plate, indicates the condition of the circuit. This multicolor LED displays red for alarm, yellow for trouble, and also green for normal operation.
The Faraday 8705 supports Style D (Class A) and Style B (Class B) wiring. Additionally, each module uses one address on the Addressable Device Circuit. Furthermore, it does not require any mechanical address programming. Use the 8720 Programmer/Tester to program and test the module.
These detector models may be mixed and matched as long as the total maximum standby current does not exceed 3.0 mA per initiating device circuit. The total number of detectors on a circuit should not exceed 30.
Features / Specifications
- Voltage Range: 18-24.5VDC
- Max. Zone Resistance 35 ohms Total
- Max Current: 100mA
- Receives its power from the 24 VDC power output
- Wire size 18 to 14 AWG