In the first place, the Edwards Est SD-TRM4 Remote Test/Reset Stations are used with the SuperDuct four-wire duct smoke detector. Also, each remote test/reset station provides a green LED to indicate power, a red LED to indicate alarms, and a yellow LED to indicate troubles and detector dirty levels. Besides, the Edwards Est SD-TRM4 requires the SD-MAG magnetic test tool. Wire the remote test/reset station to the four-wire controller as shown in Figure 2 of the datasheet below. For operating instructions, refer to technical bulletin P/N 3100685. In addition, mount the remote test/reset station on a single gang box as shown in Figure 1 of the datasheet below.
Features / Specifications
- Compatible electrical boxes: North American 1-gang box Standard 4-in square box as well as 1-1/2 inches deep, with 1-gang cover
- LED indicators: Alarm (red), Trouble (yellow), Power (green)
- LED type: Clear lens
- Wire size: 14 to 22 AWG
- Resistance per wire: 10 Ω, max
- Current requirements: included in controller specifications
- Compatible detectors: Superducts Four-Wire Duct Smoke Detectors
- Temperature: 0 to 55 °C (32 to 131 °F)
- Humidity: 93% RH, noncondensing
- Storage Temperature: -20 to 60 °C (-4 to 140 °F)
Reviews
There are no reviews yet.