In the first place, the Genesis Speaker-Strobe is a fire alarm notification appliance designed for indoor walls. The Edwards Est G4F-S2VM speaker-strobe includes field configurable switches for selecting both the desired candela output and wattage tap. Also, these settings are locked in place and remain visible after final installation.
In general, the Edwards Est G4F-S2VM strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired and the latest Canadian standard CAN/ULC S526-02. Besides, the synchronized operation requires a separately installed synchronization control module. In addition, install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code,
To install the Speaker-Strobe:
- Remove the cover by depressing the tabs on top of the unit by inserting a small screwdriver from the top and twisting it slightly
- Connect the speaker and strobe terminals to the signal circuit field wiring. You must observe polarity for the unit to function properly.
- If temporal strobe (private mode) operation is desire, cut jumper JP1.
- Slide the wattage switch to the desired wattage tap (2 W, 1 W, 1/2 W, or 1/4 W) by aligning it with the indicator notch below the switch.
- Slide the candela switch to the desired candela output (15, 30, 75, or 110 cd) by aligning it with the indicator notch below the switch.
- Mount the unit onto a compatible electrical box.
- Replace the cover by aligning it at the bottom and snapping it in at the top
- Test the unit for proper operation.
Features / Specifications
- Speaker response: 400 to 4,000 Hz
- Light output: Selectable at 15, 30, 75, and 110 cd
- Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
- Operating temperature range: 32 to 120 °F (0 to 49 °C)
- Operating humidity range: 0 to 93% RH